Victron VE.Bus BMS – BMS300200000

131,19 iva inc.

  • Shut down or disconnect the loads in a case of a sudden undervoltage in the cells.
  • Reduce the current of the charge in a case of overheating or surge of the cells (VE.Bus products).
  • Shut down or disconnect the chargers in a case of a sudden under voltage in the cells.

 

Description

Victron VE.Bus BMS

The VE.Bus BMS protects each individual cell of a Victron lithium-iron-phosphate (LiFePO4 or LFP) battery.
Each individual cell of a LiFePO4 battery must be protected against over voltage, under voltage and over temperature. Victron LiFePO4 batteries have integrated Balancing, Temperature and Voltage control (acronym: BTV) and connect to the VE.Bus BMS with two M8 circular connector cord sets. The BTVs of several batteries can be daisy chained.

The BTVs of several batteries can be daisy chained. Up to five batteries can be paralleled and up to four batteries can be series connected (BTVs are simply daisy-chained) so that a 48V battery bank of up to 1500Ah can be assembled.

The BMS will:

  • Shut down or disconnect loads in case of imminent cell under voltage.
  • Reduce charge current in case of imminent cell overvoltage or over temperature (VE.Bus products only, see below).
  • Shut down or disconnect battery chargers in case of imminent cell overvoltage or over temperature.

Protects 12V, 24V and 48V systems

The operating voltage range of the BMS: 9 to 70V DC.

Victron VE.Bus BMS communicates with all VE.Bus products

The VE.Bus BMS connects to a MultiPlus, Quattro or Phoenix inverter with a standard RJ45 UTP cable.
Other products, without VE.Bus, can be controlled as shown below:

Victron VE.Bus BMS

Load Disconnect

The Load Disconnect output is normally high and becomes free floating in case of imminent cell under voltage (default 3,1V/cell, adjustable on the battery between 2,85V and 3,15V per cell).
Maximum current: 2A.
The Load Disconnect output can be used to control

  • – the remote on/off of a load, and/or
  • – the remote on/off of an electronic load switch (Battery Protect)

Pre-alarm

The pre-alarm output is normally free floating and becomes high in case of imminent cell under voltage (default 3,1V/cell, adjustable on the battery between 2,85V and 3,15V per cell).
Maximum current: 1A (not short circuit protected).

The minimum delay between pre-alarm and load disconnect is 30 seconds.

Charge Disconnect

The Charge Disconnect output is normally high and becomes free floating in case of imminent cell over voltage or over temperature.
Maximum current: 10mA
The Charge Disconnect output can be used to control

  • – the remote on/off of a charger and/or
  • – a Cyrix-Li-Charge relay and/or
  • – a Cyrix-Li-ct Battery Combiner

LED indicators

  • – Enabled (blue): VE.Bus products are enabled.
  • Cell>> 4V or temperature (red): charge disconnect output low because of imminent cell over voltage or over temperature
  • – Cell > 2,8V (blue): load disconnect output high.

Data sheet fof the Victron VE.Bus BMS

See data sheet of the Victron VE.Bus BMS

Additional information

Weight 1 kg
Dimensions 5 × 10 × 20 cm
×